500kVA Bank Distribution Transformer
500KVA 23-2.3KV DISTRIBUTION TRANSFORMER SPECIFICATON
specification
500KVA 23-2.3KV DISTRIBUTION TRANSFORMER SPECIFICATON | |||
Clause | Description | Unit | Value |
1 | Country of Manufacture | China | |
2 | Type | Oil immersed | |
3 | Standards | IEC | IEC60076 |
4 | Rated capacity | KVA | 500 |
5 | Number of Phases | Single phase | |
6 | Frequency | Hz | 60 |
7 | Normal voltage between phase at no load | ||
i) H.V | Volts | 23000 | |
ii) L.V | Volts | 2300 | |
8 | Vector Group | Ii0 | |
9 | Off - load tapping of primary winding | % | ±2*2.5% ( 5 steps) |
10 | Rated current | ||
i ) H.V | A | 21.7 | |
ii) L.V | A | 217.4 | |
11 | Losses | ||
(a) No load loss | Watts | 860+15% | |
(c) Load loss | Watts | 7280+15% | |
12 | Impedance | % | 4 |
13 | Maximum temperature rise at C.M.R | Deg. | |
i ) Top oil / Winding | K | 60/ 65 | |
14 | Power Frequency Voltage Withstand, 1min | ||
i) H.V / L.V | kV | 50/5 | |
15 | Lightning impulse insulation level of H.V. | KV | 125 |
16 | Insulation class | A | |
17 | Insulation fluid | Mineral oil (No PCB) | |
18 | Winding material (primary/secondary) | Copper | |
19 | Ambient temp. Min/max. | ℃ | -10 ~ +40 |
20 | Method of cooling | ONAN | |
21 | Installation type | Pad Mounted | |
22 | Dimensions | ||
i ) Width & Depth & Height | mm | 1430*1220*1300 | |
23 | Color | gray | |
24 | Total Weight | kg | 1460 |
25 | standard fittings: -Nameplate -Oil level gauge -Earthing terminal -Lifting lugs -Off-load tap changer -HV & LV bushings | <span style="position:absolute;z-index:-1;margin-left:40.0000px;margin-
Contact: Erica Le Phone: 0086 13316918635 E-mail: aobest@aobest.cn SKYPE: aobestcable WhatsApp: 0086 13310857673 Add: No.260 Dongming Road, Zhengzhou city, China |