500kVA Bank Distribution Transformer

500kVA Bank Distribution Transformer

500KVA 23-2.3KV DISTRIBUTION TRANSFORMER SPECIFICATON


specification


 

500KVA 23-2.3KV DISTRIBUTION TRANSFORMER SPECIFICATON

Clause

Description

Unit

Value

1

Country of Manufacture


China

2

Type


Oil immersed

3

Standards

IEC

IEC60076

4

Rated capacity

KVA

500

5

Number of Phases


Single phase

6

Frequency

Hz

60

7

Normal voltage between phase at no load




i) H.V

Volts

23000


ii) L.V

Volts

2300

8

Vector Group


Ii0

9

Off - load tapping of primary winding

%

±2*2.5% ( 5 steps)

10

Rated current




i ) H.V

A

21.7


ii) L.V

A

217.4

11

Losses




(a) No load loss

Watts

860+15%


(c) Load loss

Watts

7280+15%

12

Impedance

%

4

13

Maximum temperature rise at C.M.R

Deg.



i ) Top oil / Winding

K

60/ 65

14

Power Frequency Voltage Withstand, 1min




i) H.V / L.V

kV

50/5

15

Lightning impulse insulation level of H.V.

KV

125

16

Insulation class


A

17

Insulation fluid


Mineral oil (No PCB)

18

Winding material (primary/secondary)


Copper

19

Ambient temp. Min/max.

-10 ~ +40

20

Method of cooling


ONAN

21

Installation type


Pad Mounted

22

Dimensions




i )   Width & Depth & Height

mm

1430*1220*1300

23

Color


gray

24

Total Weight

kg

1460

25

standard fittings:

-Nameplate                -Oil level gauge

-Earthing terminal      -Lifting lugs

-Off-load tap changer   -HV & LV bushings


<span style="position:absolute;z-index:-1;margin-left:40.0000px;margin-

PREVIOUS:insulator VHT 22T No next

INQUIRY